Pro dialog plus коды ошибок для carrier

The following list gives a complete description of each alarm

code and its possible cause.

ALARM CODE DESCRIPTIONS

Code

Alarm name

1

Evaporator leaving water thermistor fault

2

Evaporator entering water thermistor fault

3

Condenser leaving water thermistor fault

4

Condenser entering water thermistor fault

5

Heat reclaim entering water thermistor fault

6

Heat reclaim leaving water thermistor fault

7

Outdoor temperature sensor fault

8

CHWS (master/slave) fluid thermistor fault

9

Suction thermistor fault, compressor A1

10

Suction thermistor fault, compressor B1

11

External 0-10 V dc signal fault

12

Discharge pressure sensor fault, circuit A

13

Discharge pressure sensor fault, circuit B

14

Suction pressure sensor fault, circuit A

15

Suction pressure sensor fault, circuit B

16

Oil pressure sensor fault, compressor A1

17

Oil pressure sensor fault, compressor B1

18

Oil pressure sensor fault, compressor A2

19

Oil pressure sensor fault, compressor B2

20

Oil pressure sensor fault, compressor A3

21

Oil pressure sensor fault, compressor B3

22

Oil pressure sensor fault, compressor A4

23

Oil pressure sensor fault, compressor B4

24

Pumpdown pressure sensor fault, circuit A

25

Pumpdown pressure sensor fault, circuit B

26

Loss of communication with compressor board A1

27

Loss of communication with compressor board A2

28

Loss of communication with compressor board A3

29

Loss of communication with compressor board A4

30

Loss of communication with compressor board B1

31

Loss of communication with compressor board B2

32

Loss of communication with compressor board B3

33

Loss of communication with compressor board B4

34

Loss of communication with EXV board

35

Loss of communication with NRCP board

36

Loss of communication with fan board 1

37

Loss of communication with fan board 2

38

Loss of communication with 4xAI — 2xAO board 1

39

Loss of communication with 4xAI — 2xAO board 2

40

Pumpdown fault, circuit A

41

Pumpdown fault, circuit B

42

Evaporator frost protection

43

Low evaporator water flow rate.

44

Low suction temperature, circuit A

45

Low suction temperature, circuit B

46

High suction overheat, circuit A

47

High suction overheat, circuit B

48

Low suction overheat, circuit A

Description

Action

Thermistor outside range

Unit shut down

Ditto

Unit shut down

Ditto

Heating mode: Unit shut down,

if control on leaving water.

Cooling mode: no action

Ditto

Heating mode: Unit shut down,

if control on entering water.

Cooling mode: no action

Ditto

Unit with heat recalaim option:

heat reclaim mode shut down,

unit changes over to standard

cooling mode. If not: no action

Ditto

None

Ditto

Reset: normal setpoint used.

Limitation or reset deactivated.

Ditto

Deactivated

Ditto

Circuit A shut down

Ditto

Circuit B shut down

Reset signal outside range

Reset: normal setpoint used

Limitation or reset deactivated

Voltage transmitted by incorrect sensor Circuit A shut down

Ditto

Circuit B shut down

Ditto

Circuit A shut down

Ditto

Circuit B shut down

Ditto

Circuit A shut down

Ditto

Circuit B shut down

Ditto

Compressor A2 shut down

Ditto

Compressor B2 shut down

Ditto

Compressor A3 shut down

Ditto

Compressor B3 shut down

Ditto

Compressor A4 shut down

Ditto

Compressor B4 shut down

Ditto

If circuit is in heat reclaim

mode, it goes to cooling mode.

If not, no action

Ditto

Ditto

Communication with the compressor

Circuit A shut down

board is lost

Ditto

Compressor A2 shut down

Ditto

Compressor A3 shut down

Ditto

Compressor A4 shut down

Ditto

Circuit B shut down

Ditto

Compressor B2 shut down

Ditto

Compressor B3 shut down

Ditto

Compressor B4 shut down

Ditto

Unit shut down

The board does not respond

Unit shut down, if heat reclaim mode No

is selected

Ditto

Unit shut down, if the number of

fan stages per circuit is less than 3.

If not, circuit A shut down

Ditto

Circuit B shut down

Ditto

Unit shut down or no action

Ditto

Compressors or circuit shut down

End of pumpdown conditions not

Circuit A shut down

satisfied

Ditto

Circuit B shut down

Unit operating: units shut down if

Unit shut down

temp. < defrost threshold.

Unit shut down: if temp < threshold

and evaporator heater on for more

than 10 mins.

Unit shut down

Circuit operating: saturated suction

Circuit A shut down

temp. < defrost threshold and < leaving

water -16°C for more than 10 mins.

Ditto

Circuit B shut down

EXV fully open

Circuit A shut down

Ditto

Circuit B shut down

EXV in min. position, and circuit

Circuit A shut down

superheat below superheat setpoint

-5.5 K, saturated suction temp. above

MOP for 5 mins.

Pumpdown

Reset type

Probable cause

Yes

Auto

Thermistor or wiring fault or

bad connection

Yes

Auto

Ditto

Yes

Auto

Ditto

Auto

Ditto

Auto

Ditto

Auto

Ditto

Auto, if temp. mea-

Thermistor faulty

sured by sensor

returns to normal

Ditto

Themistor faulty

Yes

Auto

Ditto

Yes

Auto

Ditto

No

Auto

Signal incorrect, wiring error

Yes

Auto

Sensor fault or wiring error

Yes

Auto

Ditto

No

Auto

Ditto

No

Auto

Ditto

No

Auto

Ditto

No

Auto

Ditto

Auto

Ditto

Auto

Ditto

Auto

Ditto

Auto

Ditto

Auto

Ditto

Auto

Ditto

Auto, if press. mea-

sured by sensor

returns to normal

Ditto

Ditto

No

Auto

Wiring fault, faulty module,

incorrect module address

No

Auto

Ditto

No

Auto

Ditto

No

Auto

Ditto

No

Auto

Ditto

No

Auto

Ditto

Auto

Ditto

Auto

Ditto

No

Auto

Wiring bus faulty, incorrect

address or board faulty

Auto, if board is

NRCP board faulty

again detected

No

Auto

Wiring bus faulty, incorrect

address or board faulty

No

Auto

Ditto

No

Auto

Ditto, depending on

configuration

No

Auto

Ditto, depending on

configuration

No

Manual

EXV or sensor faulty

No

Manual

Ditto

No

Auto first time,

Low water flow or

then manual

thermistor defective

No

Manual

Water pump faulty

No

Manual

Low charge, filter dirty

ot thermistor faulty

No

Manual

Ditto

Yes

Manual

Ditto

Yes

Manual

Ditto

Yes

Manual

EXV or thermistor or

transducer defective

33

Pro-Dialog Plus 30RB – это система управления одноконтурными, двухконтурными или трехконтурными жидкостными чиллерами с воздушным охлаждением 30RВ или тепловыми насосами воздух-вода 30RQ. Система Pro-Dialog Plus управляет пуском компрессоров, что необходимо для поддержания нужной температуры воды на входе и выходе теплообменника. В режиме охлаждения система управляет работой вентиляторов для поддержания требуемого давления конденсации в каждом контуре.

Документация

 В режиме охлаждения система управляет работой вентиляторов для поддержания требуемого давления конденсации в каждом контуре. В тепловых насосах система регулирует и оптимизирует циклы размораживания каждого контура с целью минимизации уменьшения теплопроизводительности. Система Pro-Dialog Plus осуществляет постоянный мониторинг предохранительных устройств для обеспечения их надежной работы. Система Pro-Dialog Plus  также обеспечивает доступ к программе Quick Test (быстрое тестирование), контролирующей все входы и выходы.

 Все системы Pro-Dialog Plus могут работать в трех независимых режимах:
— Режим местного управления: управление машиной осуществляется командами с интерфейса пользователя.
— Режим дистанционного управления: управление машиной осуществляется удаленными контактами (контактами без напряжения).
— Режим CCN: управление машиной осуществляется командами из сети Carrier Comfort Network (CCN). В этом случае используется кабель передачи данных для соединения агрегата с коммуникационной шиной CCN.  

 Выбор режима работы осуществляется кнопкой Start/Stop(пуск/остановка). В случае автономной работы системы PRO-DIALOG Plus (в режиме местного или дистанционного управления) она сохраняет все свои возможности управления, но при этом не предусмотрено использование каких-либо возможностей сети CCN.

Электропитание всех плат осуществляется от общей шины 24 В переменного тока с заземленным нулем.
Предупреждение: При подключении плат к системе электропитания обеспечивайте правильную полярность, поскольку неправильное подключение приводит к повреждению платы.
В случае перерыва в подаче электропитания автоматически осуществляется повторный пуск агрегата без внешней команды. Но если в момент прекращения подачи электропитания имели место какие-либо ошибки, то они сохраняются  и в некоторых случаях могут воспрепятствовать повторному пуску контура или агрегата. Все платы непрерывно осуществляют контроль и индикацию работы своих электронных схем. При нормальной работе на каждой плате светится светодиод.
— На плате NRCP-BASE красный светодиод мерцает с интервалом 2 секунды, что свидетельствует о нормальной работе платы. Другая периодичность мерцания светодиода указывает на наличие неисправности платы или программного обеспечения.
— Непрерывное мерцание зеленого светодиода на всех платах свидетельствует о наличии правильной связи платы по своей внутренней шине. Отсутствие мерцания светодиода указывает на наличие неисправности в электромонтаже шины  LEN.
— Оранжевый светодиод ведущей платы мерцает в течение сеанса связи через шину CCN.

 Датчики давления
Для измерения давлений нагнетания и всасывания в каждомконтуре используются электронные датчики двух типов.

 Термисторы
Датчики температуры воды испарителя установлены навходе и выходе. Датчик температуры наружного воздуха установлен под блоком управления. Для регулирования работы комплекса «ведомый/ведущий» (в случае необходимости регулирования выходящей воды) может быть
установлен дополнительный датчик температуры в системе циркуляции воды. 

  • Contents

  • Table of Contents

  • Troubleshooting

  • Bookmarks

Quick Links

30GK Series

PRO-DIALOG

Control

Air-Cooled Liquid Chillers

50 Hz

Installation, operation and maintenance instructions

1

loading

Related Manuals for Carrier PRO-DIALOG Plus 30GK Series

Summary of Contents for Carrier PRO-DIALOG Plus 30GK Series

  • Page 1
    30GK Series PRO-DIALOG Control Air-Cooled Liquid Chillers 50 Hz Installation, operation and maintenance instructions…
  • Page 2: Table Of Contents

    TABLE OF CONTENTS 1 — SAFETY CONSIDERATIONS …………………………4 1.1 — General ………………………………4 1.2 — Avoiding electrocution …………………………… 4 2 — GENERAL DESCRIPTION …………………………5 2.1 — General ………………………………5 2.2 — Abbreviations used …………………………..5 3 — HARDWARE DESCRIPTION …………………………6 3.1 — General ………………………………

  • Page 3
    5 — PRO-DIALOG PLUS CONTROL OPERATION ……………………. 27 5.1 — Start/stop control …………………………..27 5.2 — Heating/cooling selection …………………………27 5.3 — Evaporator water pump control ……………………….28 5.4 — Condenser water pump control ……………………….28 5.5 — Control interlock contact …………………………28 5.6 — Evaporator heater control …………………………
  • Page 4: Safety Considerations

    1 — SAFETY CONSIDERATIONS IMPORTANT: Risk of electrocution: Even when the main power isolator or 1.1 — General circuit breaker is off, it is still possible for certain compo- nents such as crankcase heaters and trace heaters to be Installation, start-up and servicing of equipment can be hazard- energised, since they are connected to a separate power source.

  • Page 5: General Description

    (volt-free contacts, analogue signals). • CCN mode: the machine is controlled by commands from the Carrier Comfort Network (CCN). In this case a data communication cable is used to connect the unit to the CCN communication bus. The operating mode must be chosen with the Operating Type selection button described in section 4.2.1.

  • Page 6: Hardware Description

    SIO bus. It can also communicate with elements of the Carrier Comfort Network via the CCN bus. Legend CCN connector…

  • Page 7: The User Interface

    3.2.7 — Light emitting diodes on boards 3.2.3 — The user interface All boards continuously check and indicate the proper The user interface is in two parts: operation of their electronic circuits. A light emitting diode • The main interface: This gives access to all of the (LED) lights on each board when it is operating properly.

  • Page 8: The Evaporator Pumps

    The sensor is not They are located in the low-pressure side of the unit on the lead supplied by Carrier, and must be configured by the User Menu. compressor of each circuit. The suction pressure sensor reading is used to control the electronic expansion devices EXV.

  • Page 9: User Connections

    3.4 — User connections The connections below are available at the customer’s terminal block. Some of them can only be used in special operating modes. For further details see the sections that describe the functions (section 5) and the configurations (section 4.2.1). NOTE: The bridge between terminals 32, 63 and 65 on the customer’s terminal block must not be removed.

  • Page 10: Setting Up Pro-Dialog Plus Control

    4 — SETTING UP PRO-DIALOG PLUS CONTROL 4.1 — Local interface general features MAIN INTERFACE SUMMARY INTERFACE MAIN INTERFACE SUMMARY INTERFACE DUAL-CIRCUIT AIR-COOLED DUAL-CIRCUIT WATER-COOLED CHILLER INTERFACE CHILLER INTERFACE MENU BLOCK MENU BLOCK The local interface enables a number of operating parameters to Main interface be displayed and modified.

  • Page 11: Unit Start/Stop Control

    The summary interface (right hand section) includes a mimic The following operating types can be selected using the diagram of the unit, together with push-buttons and LEDs. It Start/Stop button: gives quick access to the main operating parameters of the unit. OPERATING TYPES SUMMARY INTERFACE LEDS 4-DIGIT DISPLAY DESCRIPTION…

  • Page 12: Menus

    4.3 — Menus NOTE: The access to a sub-menu may require entering a password. This is automatically requested. See section 4.5.7.2. 4.3.1 — Selecting a menu The MENU button authorises you to select a menu from the 10 The example below shows how to modify the value of item 1 main menus that are available.

  • Page 13: General Menu Structure

    4.4 — General menu structure…

  • Page 14: Menu Tree Structure

    4.5 — Menu tree structure MENU…

  • Page 15: Description Of The Information Menu

    4.5.1 — Description of the Information menu INFORMATION MENU [3] ITEM FORMAT UNITS DESCRIPTION Automatic display mode. It cycles through the following displays: ±nn.n °C Controlled water temperature: temperature of the water that the unit tries to maintain at the control point. Unit operating type LOFF Local Off…

  • Page 16: Description Of The Temperatures Menu

    DESCRIPTION OF OPERATING MODES (ITEM 1 OF THE INFORMATION MENU) MODE # MODE NAME DESCRIPTION Delay at start-up active The delay at start-up operates after the unit has been switched on. If the delay has not expired, the mode is active. The delay is configured in the User1 configuration menu.

  • Page 17: Description Of The Setpoints Menu

    4.5.4 — Description of the Setpoints menu SETPOINTS MENU [2] ITEM FORMAT UNITS RANGE COMMENTS ±nn.n °C See table below This item lets you display and modify Cooling setpoint 1* ±nn.n °C See table below This item lets you display and modify Cooling setpoint 2* °C See table below This item lets you display and modify Heating setpoint*, only displayed for heat pumps.

  • Page 18: Description Of The Inputs Menu

    4.5.5 — Description of the Inputs menu INPUTS MENU [2] ITEM FORMAT UNITS COMMENTS OPEn/CLoS Remote contact 1 status This contact is used to start (contact closed) and stop (contact open) the chiller. It is only valid, if the unit is in the remote operating control (rEM) mode.

  • Page 19
    OUTPUTS STATUS 2 AND TESTS MENU [2] [3] — cont. ITEM FORMAT UNITS DESCRIPTION 4 [1] tESt Fan contactor status/test, circuit B b1 = fan contactor assembly 1 b2 = fan contactor assembly 2 b3 = fan contactor assembly 3 b4 = fan contactor assembly 4 This item permits display of the fan stages.
  • Page 20: Description Of The Configuration Menu

    4.5.6.3 — Manual tests The menus User 1 [USEr 1] and User 2 [USEr 2] are pass- This function allows the user to test the outputs individually, if word-protected. The other menus are directly accessible, except the machine is completely shut down (LOFF). To carry out a if item 12 of the User 1 menu (password for all configurations) manual test use the arrow keys to access the output to be tested has been validated.

  • Page 21: User Interface

    CONFIGURATION USER [USEr] USER1 USER2 SCHEDULE 1 SCHEDULE 2 HOLIDAYS HOUR + DATE BROADCAST [USEr 1] [USEr 2] [SCHEduLE 1]* [SCHEduLE 2]* [HOLIDAYS]* [dAtE]* [broAdCASE]* PERIOD 1 PERIOD 1 HOLIDAY 1 PERIOD 2 PERIOD 2 HOLIDAY 2 PERIOD 3 PERIOD 3 HOLIDAY 3 HOLIDAY 4 PERIOD 4…

  • Page 22
    4.5.7.3 — Description of the User 1 Configuration sub-menu USER 1 CONFIGURATION SUB-MENU [2] ITEM FORMAT UNITS DEFAULT COMMENTS USEr MEnu When selected this item authorises return to the previous menu. 1 [1] 0/1/2 Lead circuit selection 0 = automatic based on the number of start-ups and the operating hours of each circuit 1 = lead circuit A 2 = lead circuit B 2 [1]…
  • Page 23
    4.5.7.4 — Description of the User 2 Configuration sub-menu USER 1 CONFIGURATION SUB-MENU ITEM FORMAT UNITS DEFAULT COMMENTS USEr 2 Menu When selected this item authorises return to the previous menu. 1[1] YES/no Periodic pump quick-start of the water pump(s) Yes = the pump is started periodically when the unit is manually stopped.
  • Page 24
    PERIOD X CONFIGURATION SUB-MENUS (X = 1 to 8) 4.5.7.7 — Description of the Holidays sub-menus ITEM # FORMAT COMMENTS This function is used to define 16 public holiday periods. Each Period X Menu Indicates the period (X) you are going to period is defined with the aid of three parameters: the month, configure.
  • Page 25: Description Of The Alarms Menu

    BROADCAST CONFIGURATION SUB-MENU ITEM # FORMAT COMMENTS broAdCASt MEnu When selected this item authorises a return to the main menu. YES/no Determines whether or not the unit is a broadcast acknowledger when the unit is connected on a CCN network. There must be only one broadcast acknowledger in a CCN.

  • Page 26: Runtime Menu Description

    4.5.10 — Runtime menu description 4.5.10.2 — Description of the Runtimes 2 menu RUNTIMES MENU [2] RUNTIMES iTEM # FORMAT UNIT COMMENTS When selected this item authorises return to the previous menu RUNTIMES 1 RUNTIMES 2 MAINTENANCE [runtiMES 1] [runtiMES 2] [MAintEnAnCE] nnnn | M 10 | M100 hrs/10 or 100…

  • Page 27: Pro-Dialog Plus Control Operation

    5 — PRO-DIALOG PLUS CONTROL OPERATION Start/Stop schedule: occupied or unoccupied status of the unit as determined by the chiller start/stop program 5.1 — Start/stop control (Schedule #1). Used when the unit is equipped with an optional CCN/clock board, otherwise the chiller occupied The table below summarises the unit control type and stop or mode is forced to occupied all the time.

  • Page 28: Evaporator Water Pump Control

    The condenser pump can be controlled by two modes, depend- Plus control system, the source of the reset can be configured ing on the configuration (only accessible by Carrier Service). in the User 1 configuration: it can be based on an external 0-10 V 1 — Control based on unit start/stop control.

  • Page 29: Demand Limit

    5.8 — Demand limit NOTE: If the same compressor undergoes too many starts (per hour) this automatically brings about reduction of Generally, demand limit is used by an energy management compressor starts, which makes leaving water temperature system in order to restrict the unit electricity consumption. control less precise.

  • Page 30: Slave Compressor Start-Up Sequence

    5.14 — Head pressure control on air-cooled units as a function of the control typpes (local, remote or network), and the parameters below: There are two methods, configurable only by Carrier Service, • Local setpoint selection: item No. 11 of the Information…

  • Page 31: High Pressure Load Shedding Function

    LOCAL OPERATING MODE PARAMETER STATUS All control commands to the master/slave assembly (start/stop, HEATING/ LOCAL SCHEDULE 2 ACTIVE SETPOINT setpoint, heating/cooling operation, load shedding, etc.) are COOLING SETPOINT PROGRAM STATUS handled by the unit which is configured as the master, and must OPERATING SELECTION MODE…

  • Page 32: Optional Heat Reclaim Module

    5.21 — Optional heat reclaim module 6 — DIAGNOSTICS — TROUBLESHOOTING Change-over procedure from cooling mode to heat reclaim 6.1 — General mode: • Start-up of the condenser pump The PRO-DIALOG Plus control system has many fault tracing • Verification of the condenser flow switch control contact. aid functions.

  • Page 33: Alarm Codes

    6.4 — Alarm codes The following list gives a complete description of each alarm code and its possible cause. ALARM CODE DESCRIPTIONS Code Alarm name Description Action Pumpdown Reset type Probable cause Evaporator leaving water thermistor fault Thermistor outside range Unit shut down Auto Thermistor or wiring fault or…

  • Page 34
    ALARM CODE DESCRIPTIONS Code Alarm name Description Action Pumpdown Reset type Probable cause Low suction overheat, circuit B Circuit B shut down Manual Ditto Low oil pressure, compressor A1 Oil pressure < min. threshold Circuit A shut down Manual Compressor, crankcase heater, pressure sensor or EXV faulty, refrigerant charge too high, low oil…
  • Page 35: Compressor Faults

    This board patented by Carrier (also called AM board) monitors both the compressor regime and the status of its crankcase heaters which ensure correct lubrication when the 6.4.1.2 — Compressor protection devices…

  • Page 36
    Order No. 13040-76, 05.2000. Supersedes order No.: New Manufactured by: Carrier S.A., Montluel, France. Manufacturer reserves the right to change any product specifications without notice. Printed in the Netherlands on totally chlorine-free paper.

Понравилась статья? Поделить с друзьями:
  • Pro cl 200 ошибка c2 255
  • Pro cl 200 ошибка c2 233
  • Prnds ауди ошибка на панели приборов
  • Prison break the conspiracy не запускается выдает ошибку
  • Prison architect ошибка связи со steam