The following list gives a complete description of each alarm
code and its possible cause.
ALARM CODE DESCRIPTIONS
Code
Alarm name
1
Evaporator leaving water thermistor fault
2
Evaporator entering water thermistor fault
3
Condenser leaving water thermistor fault
4
Condenser entering water thermistor fault
5
Heat reclaim entering water thermistor fault
6
Heat reclaim leaving water thermistor fault
7
Outdoor temperature sensor fault
8
CHWS (master/slave) fluid thermistor fault
9
Suction thermistor fault, compressor A1
10
Suction thermistor fault, compressor B1
11
External 0-10 V dc signal fault
12
Discharge pressure sensor fault, circuit A
13
Discharge pressure sensor fault, circuit B
14
Suction pressure sensor fault, circuit A
15
Suction pressure sensor fault, circuit B
16
Oil pressure sensor fault, compressor A1
17
Oil pressure sensor fault, compressor B1
18
Oil pressure sensor fault, compressor A2
19
Oil pressure sensor fault, compressor B2
20
Oil pressure sensor fault, compressor A3
21
Oil pressure sensor fault, compressor B3
22
Oil pressure sensor fault, compressor A4
23
Oil pressure sensor fault, compressor B4
24
Pumpdown pressure sensor fault, circuit A
25
Pumpdown pressure sensor fault, circuit B
26
Loss of communication with compressor board A1
27
Loss of communication with compressor board A2
28
Loss of communication with compressor board A3
29
Loss of communication with compressor board A4
30
Loss of communication with compressor board B1
31
Loss of communication with compressor board B2
32
Loss of communication with compressor board B3
33
Loss of communication with compressor board B4
34
Loss of communication with EXV board
35
Loss of communication with NRCP board
36
Loss of communication with fan board 1
37
Loss of communication with fan board 2
38
Loss of communication with 4xAI — 2xAO board 1
39
Loss of communication with 4xAI — 2xAO board 2
40
Pumpdown fault, circuit A
41
Pumpdown fault, circuit B
42
Evaporator frost protection
43
Low evaporator water flow rate.
44
Low suction temperature, circuit A
45
Low suction temperature, circuit B
46
High suction overheat, circuit A
47
High suction overheat, circuit B
48
Low suction overheat, circuit A
Description
Action
Thermistor outside range
Unit shut down
Ditto
Unit shut down
Ditto
Heating mode: Unit shut down,
if control on leaving water.
Cooling mode: no action
Ditto
Heating mode: Unit shut down,
if control on entering water.
Cooling mode: no action
Ditto
Unit with heat recalaim option:
heat reclaim mode shut down,
unit changes over to standard
cooling mode. If not: no action
Ditto
None
Ditto
Reset: normal setpoint used.
Limitation or reset deactivated.
Ditto
Deactivated
Ditto
Circuit A shut down
Ditto
Circuit B shut down
Reset signal outside range
Reset: normal setpoint used
Limitation or reset deactivated
Voltage transmitted by incorrect sensor Circuit A shut down
Ditto
Circuit B shut down
Ditto
Circuit A shut down
Ditto
Circuit B shut down
Ditto
Circuit A shut down
Ditto
Circuit B shut down
Ditto
Compressor A2 shut down
Ditto
Compressor B2 shut down
Ditto
Compressor A3 shut down
Ditto
Compressor B3 shut down
Ditto
Compressor A4 shut down
Ditto
Compressor B4 shut down
Ditto
If circuit is in heat reclaim
mode, it goes to cooling mode.
If not, no action
Ditto
Ditto
Communication with the compressor
Circuit A shut down
board is lost
Ditto
Compressor A2 shut down
Ditto
Compressor A3 shut down
Ditto
Compressor A4 shut down
Ditto
Circuit B shut down
Ditto
Compressor B2 shut down
Ditto
Compressor B3 shut down
Ditto
Compressor B4 shut down
Ditto
Unit shut down
The board does not respond
Unit shut down, if heat reclaim mode No
is selected
Ditto
Unit shut down, if the number of
fan stages per circuit is less than 3.
If not, circuit A shut down
Ditto
Circuit B shut down
Ditto
Unit shut down or no action
Ditto
Compressors or circuit shut down
End of pumpdown conditions not
Circuit A shut down
satisfied
Ditto
Circuit B shut down
Unit operating: units shut down if
Unit shut down
temp. < defrost threshold.
Unit shut down: if temp < threshold
and evaporator heater on for more
than 10 mins.
Unit shut down
Circuit operating: saturated suction
Circuit A shut down
temp. < defrost threshold and < leaving
water -16°C for more than 10 mins.
Ditto
Circuit B shut down
EXV fully open
Circuit A shut down
Ditto
Circuit B shut down
EXV in min. position, and circuit
Circuit A shut down
superheat below superheat setpoint
-5.5 K, saturated suction temp. above
MOP for 5 mins.
Pumpdown
Reset type
Probable cause
Yes
Auto
Thermistor or wiring fault or
bad connection
Yes
Auto
Ditto
Yes
Auto
Ditto
—
Auto
Ditto
—
Auto
Ditto
—
Auto
Ditto
—
Auto, if temp. mea-
Thermistor faulty
sured by sensor
returns to normal
—
Ditto
Themistor faulty
Yes
Auto
Ditto
Yes
Auto
Ditto
No
Auto
Signal incorrect, wiring error
Yes
Auto
Sensor fault or wiring error
Yes
Auto
Ditto
No
Auto
Ditto
No
Auto
Ditto
No
Auto
Ditto
No
Auto
Ditto
—
Auto
Ditto
—
Auto
Ditto
—
Auto
Ditto
—
Auto
Ditto
—
Auto
Ditto
—
Auto
Ditto
—
Auto, if press. mea-
sured by sensor
returns to normal
—
Ditto
Ditto
No
Auto
Wiring fault, faulty module,
incorrect module address
No
Auto
Ditto
No
Auto
Ditto
No
Auto
Ditto
No
Auto
Ditto
No
Auto
Ditto
—
Auto
Ditto
—
Auto
Ditto
No
Auto
Wiring bus faulty, incorrect
address or board faulty
Auto, if board is
NRCP board faulty
again detected
No
Auto
Wiring bus faulty, incorrect
address or board faulty
No
Auto
Ditto
No
Auto
Ditto, depending on
configuration
No
Auto
Ditto, depending on
configuration
No
Manual
EXV or sensor faulty
No
Manual
Ditto
No
Auto first time,
Low water flow or
then manual
thermistor defective
No
Manual
Water pump faulty
No
Manual
Low charge, filter dirty
ot thermistor faulty
No
Manual
Ditto
Yes
Manual
Ditto
Yes
Manual
Ditto
Yes
Manual
EXV or thermistor or
transducer defective
33
Pro-Dialog Plus 30RB – это система управления одноконтурными, двухконтурными или трехконтурными жидкостными чиллерами с воздушным охлаждением 30RВ или тепловыми насосами воздух-вода 30RQ. Система Pro-Dialog Plus управляет пуском компрессоров, что необходимо для поддержания нужной температуры воды на входе и выходе теплообменника. В режиме охлаждения система управляет работой вентиляторов для поддержания требуемого давления конденсации в каждом контуре.
Документация
В режиме охлаждения система управляет работой вентиляторов для поддержания требуемого давления конденсации в каждом контуре. В тепловых насосах система регулирует и оптимизирует циклы размораживания каждого контура с целью минимизации уменьшения теплопроизводительности. Система Pro-Dialog Plus осуществляет постоянный мониторинг предохранительных устройств для обеспечения их надежной работы. Система Pro-Dialog Plus также обеспечивает доступ к программе Quick Test (быстрое тестирование), контролирующей все входы и выходы.
Все системы Pro-Dialog Plus могут работать в трех независимых режимах:
— Режим местного управления: управление машиной осуществляется командами с интерфейса пользователя.
— Режим дистанционного управления: управление машиной осуществляется удаленными контактами (контактами без напряжения).
— Режим CCN: управление машиной осуществляется командами из сети Carrier Comfort Network (CCN). В этом случае используется кабель передачи данных для соединения агрегата с коммуникационной шиной CCN.
Выбор режима работы осуществляется кнопкой Start/Stop(пуск/остановка). В случае автономной работы системы PRO-DIALOG Plus (в режиме местного или дистанционного управления) она сохраняет все свои возможности управления, но при этом не предусмотрено использование каких-либо возможностей сети CCN.
Электропитание всех плат осуществляется от общей шины 24 В переменного тока с заземленным нулем.
Предупреждение: При подключении плат к системе электропитания обеспечивайте правильную полярность, поскольку неправильное подключение приводит к повреждению платы.
В случае перерыва в подаче электропитания автоматически осуществляется повторный пуск агрегата без внешней команды. Но если в момент прекращения подачи электропитания имели место какие-либо ошибки, то они сохраняются и в некоторых случаях могут воспрепятствовать повторному пуску контура или агрегата. Все платы непрерывно осуществляют контроль и индикацию работы своих электронных схем. При нормальной работе на каждой плате светится светодиод.
— На плате NRCP-BASE красный светодиод мерцает с интервалом 2 секунды, что свидетельствует о нормальной работе платы. Другая периодичность мерцания светодиода указывает на наличие неисправности платы или программного обеспечения.
— Непрерывное мерцание зеленого светодиода на всех платах свидетельствует о наличии правильной связи платы по своей внутренней шине. Отсутствие мерцания светодиода указывает на наличие неисправности в электромонтаже шины LEN.
— Оранжевый светодиод ведущей платы мерцает в течение сеанса связи через шину CCN.
Датчики давления
Для измерения давлений нагнетания и всасывания в каждомконтуре используются электронные датчики двух типов.
Термисторы
Датчики температуры воды испарителя установлены навходе и выходе. Датчик температуры наружного воздуха установлен под блоком управления. Для регулирования работы комплекса «ведомый/ведущий» (в случае необходимости регулирования выходящей воды) может быть
установлен дополнительный датчик температуры в системе циркуляции воды.
-
Contents
-
Table of Contents
-
Troubleshooting
-
Bookmarks
Quick Links
30GK Series
PRO-DIALOG
Control
Air-Cooled Liquid Chillers
50 Hz
Installation, operation and maintenance instructions
1
Related Manuals for Carrier PRO-DIALOG Plus 30GK Series
Summary of Contents for Carrier PRO-DIALOG Plus 30GK Series
-
Page 1
30GK Series PRO-DIALOG Control Air-Cooled Liquid Chillers 50 Hz Installation, operation and maintenance instructions… -
Page 2: Table Of Contents
TABLE OF CONTENTS 1 — SAFETY CONSIDERATIONS …………………………4 1.1 — General ………………………………4 1.2 — Avoiding electrocution …………………………… 4 2 — GENERAL DESCRIPTION …………………………5 2.1 — General ………………………………5 2.2 — Abbreviations used …………………………..5 3 — HARDWARE DESCRIPTION …………………………6 3.1 — General ………………………………
-
Page 3
5 — PRO-DIALOG PLUS CONTROL OPERATION ……………………. 27 5.1 — Start/stop control …………………………..27 5.2 — Heating/cooling selection …………………………27 5.3 — Evaporator water pump control ……………………….28 5.4 — Condenser water pump control ……………………….28 5.5 — Control interlock contact …………………………28 5.6 — Evaporator heater control ………………………… -
Page 4: Safety Considerations
1 — SAFETY CONSIDERATIONS IMPORTANT: Risk of electrocution: Even when the main power isolator or 1.1 — General circuit breaker is off, it is still possible for certain compo- nents such as crankcase heaters and trace heaters to be Installation, start-up and servicing of equipment can be hazard- energised, since they are connected to a separate power source.
-
Page 5: General Description
(volt-free contacts, analogue signals). • CCN mode: the machine is controlled by commands from the Carrier Comfort Network (CCN). In this case a data communication cable is used to connect the unit to the CCN communication bus. The operating mode must be chosen with the Operating Type selection button described in section 4.2.1.
-
Page 6: Hardware Description
SIO bus. It can also communicate with elements of the Carrier Comfort Network via the CCN bus. Legend CCN connector…
-
Page 7: The User Interface
3.2.7 — Light emitting diodes on boards 3.2.3 — The user interface All boards continuously check and indicate the proper The user interface is in two parts: operation of their electronic circuits. A light emitting diode • The main interface: This gives access to all of the (LED) lights on each board when it is operating properly.
-
Page 8: The Evaporator Pumps
The sensor is not They are located in the low-pressure side of the unit on the lead supplied by Carrier, and must be configured by the User Menu. compressor of each circuit. The suction pressure sensor reading is used to control the electronic expansion devices EXV.
-
Page 9: User Connections
3.4 — User connections The connections below are available at the customer’s terminal block. Some of them can only be used in special operating modes. For further details see the sections that describe the functions (section 5) and the configurations (section 4.2.1). NOTE: The bridge between terminals 32, 63 and 65 on the customer’s terminal block must not be removed.
-
Page 10: Setting Up Pro-Dialog Plus Control
4 — SETTING UP PRO-DIALOG PLUS CONTROL 4.1 — Local interface general features MAIN INTERFACE SUMMARY INTERFACE MAIN INTERFACE SUMMARY INTERFACE DUAL-CIRCUIT AIR-COOLED DUAL-CIRCUIT WATER-COOLED CHILLER INTERFACE CHILLER INTERFACE MENU BLOCK MENU BLOCK The local interface enables a number of operating parameters to Main interface be displayed and modified.
-
Page 11: Unit Start/Stop Control
The summary interface (right hand section) includes a mimic The following operating types can be selected using the diagram of the unit, together with push-buttons and LEDs. It Start/Stop button: gives quick access to the main operating parameters of the unit. OPERATING TYPES SUMMARY INTERFACE LEDS 4-DIGIT DISPLAY DESCRIPTION…
-
Page 12: Menus
4.3 — Menus NOTE: The access to a sub-menu may require entering a password. This is automatically requested. See section 4.5.7.2. 4.3.1 — Selecting a menu The MENU button authorises you to select a menu from the 10 The example below shows how to modify the value of item 1 main menus that are available.
-
Page 13: General Menu Structure
4.4 — General menu structure…
-
Page 14: Menu Tree Structure
4.5 — Menu tree structure MENU…
-
Page 15: Description Of The Information Menu
4.5.1 — Description of the Information menu INFORMATION MENU [3] ITEM FORMAT UNITS DESCRIPTION Automatic display mode. It cycles through the following displays: ±nn.n °C Controlled water temperature: temperature of the water that the unit tries to maintain at the control point. Unit operating type LOFF Local Off…
-
Page 16: Description Of The Temperatures Menu
DESCRIPTION OF OPERATING MODES (ITEM 1 OF THE INFORMATION MENU) MODE # MODE NAME DESCRIPTION Delay at start-up active The delay at start-up operates after the unit has been switched on. If the delay has not expired, the mode is active. The delay is configured in the User1 configuration menu.
-
Page 17: Description Of The Setpoints Menu
4.5.4 — Description of the Setpoints menu SETPOINTS MENU [2] ITEM FORMAT UNITS RANGE COMMENTS ±nn.n °C See table below This item lets you display and modify Cooling setpoint 1* ±nn.n °C See table below This item lets you display and modify Cooling setpoint 2* °C See table below This item lets you display and modify Heating setpoint*, only displayed for heat pumps.
-
Page 18: Description Of The Inputs Menu
4.5.5 — Description of the Inputs menu INPUTS MENU [2] ITEM FORMAT UNITS COMMENTS OPEn/CLoS Remote contact 1 status This contact is used to start (contact closed) and stop (contact open) the chiller. It is only valid, if the unit is in the remote operating control (rEM) mode.
-
Page 19
OUTPUTS STATUS 2 AND TESTS MENU [2] [3] — cont. ITEM FORMAT UNITS DESCRIPTION 4 [1] tESt Fan contactor status/test, circuit B b1 = fan contactor assembly 1 b2 = fan contactor assembly 2 b3 = fan contactor assembly 3 b4 = fan contactor assembly 4 This item permits display of the fan stages. -
Page 20: Description Of The Configuration Menu
4.5.6.3 — Manual tests The menus User 1 [USEr 1] and User 2 [USEr 2] are pass- This function allows the user to test the outputs individually, if word-protected. The other menus are directly accessible, except the machine is completely shut down (LOFF). To carry out a if item 12 of the User 1 menu (password for all configurations) manual test use the arrow keys to access the output to be tested has been validated.
-
Page 21: User Interface
CONFIGURATION USER [USEr] USER1 USER2 SCHEDULE 1 SCHEDULE 2 HOLIDAYS HOUR + DATE BROADCAST [USEr 1] [USEr 2] [SCHEduLE 1]* [SCHEduLE 2]* [HOLIDAYS]* [dAtE]* [broAdCASE]* PERIOD 1 PERIOD 1 HOLIDAY 1 PERIOD 2 PERIOD 2 HOLIDAY 2 PERIOD 3 PERIOD 3 HOLIDAY 3 HOLIDAY 4 PERIOD 4…
-
Page 22
4.5.7.3 — Description of the User 1 Configuration sub-menu USER 1 CONFIGURATION SUB-MENU [2] ITEM FORMAT UNITS DEFAULT COMMENTS USEr MEnu When selected this item authorises return to the previous menu. 1 [1] 0/1/2 Lead circuit selection 0 = automatic based on the number of start-ups and the operating hours of each circuit 1 = lead circuit A 2 = lead circuit B 2 [1]… -
Page 23
4.5.7.4 — Description of the User 2 Configuration sub-menu USER 1 CONFIGURATION SUB-MENU ITEM FORMAT UNITS DEFAULT COMMENTS USEr 2 Menu When selected this item authorises return to the previous menu. 1[1] YES/no Periodic pump quick-start of the water pump(s) Yes = the pump is started periodically when the unit is manually stopped. -
Page 24
PERIOD X CONFIGURATION SUB-MENUS (X = 1 to 4.5.7.7 — Description of the Holidays sub-menus ITEM # FORMAT COMMENTS This function is used to define 16 public holiday periods. Each Period X Menu Indicates the period (X) you are going to period is defined with the aid of three parameters: the month, configure. -
Page 25: Description Of The Alarms Menu
BROADCAST CONFIGURATION SUB-MENU ITEM # FORMAT COMMENTS broAdCASt MEnu When selected this item authorises a return to the main menu. YES/no Determines whether or not the unit is a broadcast acknowledger when the unit is connected on a CCN network. There must be only one broadcast acknowledger in a CCN.
-
Page 26: Runtime Menu Description
4.5.10 — Runtime menu description 4.5.10.2 — Description of the Runtimes 2 menu RUNTIMES MENU [2] RUNTIMES iTEM # FORMAT UNIT COMMENTS When selected this item authorises return to the previous menu RUNTIMES 1 RUNTIMES 2 MAINTENANCE [runtiMES 1] [runtiMES 2] [MAintEnAnCE] nnnn | M 10 | M100 hrs/10 or 100…
-
Page 27: Pro-Dialog Plus Control Operation
5 — PRO-DIALOG PLUS CONTROL OPERATION Start/Stop schedule: occupied or unoccupied status of the unit as determined by the chiller start/stop program 5.1 — Start/stop control (Schedule #1). Used when the unit is equipped with an optional CCN/clock board, otherwise the chiller occupied The table below summarises the unit control type and stop or mode is forced to occupied all the time.
-
Page 28: Evaporator Water Pump Control
The condenser pump can be controlled by two modes, depend- Plus control system, the source of the reset can be configured ing on the configuration (only accessible by Carrier Service). in the User 1 configuration: it can be based on an external 0-10 V 1 — Control based on unit start/stop control.
-
Page 29: Demand Limit
5.8 — Demand limit NOTE: If the same compressor undergoes too many starts (per hour) this automatically brings about reduction of Generally, demand limit is used by an energy management compressor starts, which makes leaving water temperature system in order to restrict the unit electricity consumption. control less precise.
-
Page 30: Slave Compressor Start-Up Sequence
5.14 — Head pressure control on air-cooled units as a function of the control typpes (local, remote or network), and the parameters below: There are two methods, configurable only by Carrier Service, • Local setpoint selection: item No. 11 of the Information…
-
Page 31: High Pressure Load Shedding Function
LOCAL OPERATING MODE PARAMETER STATUS All control commands to the master/slave assembly (start/stop, HEATING/ LOCAL SCHEDULE 2 ACTIVE SETPOINT setpoint, heating/cooling operation, load shedding, etc.) are COOLING SETPOINT PROGRAM STATUS handled by the unit which is configured as the master, and must OPERATING SELECTION MODE…
-
Page 32: Optional Heat Reclaim Module
5.21 — Optional heat reclaim module 6 — DIAGNOSTICS — TROUBLESHOOTING Change-over procedure from cooling mode to heat reclaim 6.1 — General mode: • Start-up of the condenser pump The PRO-DIALOG Plus control system has many fault tracing • Verification of the condenser flow switch control contact. aid functions.
-
Page 33: Alarm Codes
6.4 — Alarm codes The following list gives a complete description of each alarm code and its possible cause. ALARM CODE DESCRIPTIONS Code Alarm name Description Action Pumpdown Reset type Probable cause Evaporator leaving water thermistor fault Thermistor outside range Unit shut down Auto Thermistor or wiring fault or…
-
Page 34
ALARM CODE DESCRIPTIONS Code Alarm name Description Action Pumpdown Reset type Probable cause Low suction overheat, circuit B Circuit B shut down Manual Ditto Low oil pressure, compressor A1 Oil pressure < min. threshold Circuit A shut down Manual Compressor, crankcase heater, pressure sensor or EXV faulty, refrigerant charge too high, low oil… -
Page 35: Compressor Faults
This board patented by Carrier (also called AM board) monitors both the compressor regime and the status of its crankcase heaters which ensure correct lubrication when the 6.4.1.2 — Compressor protection devices…
-
Page 36
Order No. 13040-76, 05.2000. Supersedes order No.: New Manufactured by: Carrier S.A., Montluel, France. Manufacturer reserves the right to change any product specifications without notice. Printed in the Netherlands on totally chlorine-free paper.